Life Safety and Fire Fighting Systems – The weakest hyperlink

Unlike different cables, fire resistant cables should work even when directly exposed to the hearth to maintain essential Life Safety and Fire Fighting gear working: Fire alarms, Emergency Lighting, Emergency Communication, Fire Sprinkler pumps, Fireman’s Lift sub-main, Smoke extraction fans, Smoke dampers, Stair pressurization followers, Emergency Generator circuits and so forth.
In order to classify electrical cables as fireplace resistant they are required to undergo testing and certification. Perhaps the first common hearth exams on cables have been IEC 331: 1970 and later BS6387:1983 which adopted a gas ribbon burner test to produce a flame during which cables were positioned.
Since the revision of BS6387 in 1994 there have been eleven enhancements, revisions or new take a look at requirements launched by British Standards for use and utility of Fire Resistant cables but none of these seem to handle the core concern that fire resistant cables the place examined to common British and IEC flame take a look at standards usually are not required to carry out to the identical fire performance time-temperature profiles as every other structure, system or element in a constructing. Specifically, where เกจแรงดันลม , techniques, partitions, fireplace doors, fireplace penetrations fire obstacles, floors, walls and so forth. are required to be fireplace rated by constructing regulations, they’re tested to the Standard Time Temperature protocol of BS476 components 20 to 23 (also generally recognized as ISO834-1, ASNZS1530pt4, EN1363-1 and in America and Canada ASTM E119-75).
These tests are performed in massive furnaces to copy real post flashover fire environments. Interestingly, Fire Resistant cable check requirements like BS 6387CWZ, SS299, IEC 60331 BS8343-1 and a pair of, BS8491 only require cables to be uncovered to a flame in air and to decrease final check temperatures (than required by BS476 pts 20 to 23). Given Fire Resistant cables are likely to be uncovered in the identical hearth, and are needed to make sure all Life Safety and Fire Fighting systems stay operational, this reality is perhaps shocking.
Contrastingly in Germany, Belgium, Australia, New Zealand, USA and Canada Fire Resistant cable methods are required to be tested to the same hearth Time Temperature protocol as all other constructing parts and this is the Standard Time Temperature protocol to BS476pts 20-23, IS0 834-1, EN1363-1 or ASTM E119-75 in USA.
The committees growing the standard drew on the steerage given from the International Fire Prevention Congress held in London in July 1903 and the measurements of furnace temperatures made in lots of fireplace exams carried out in the UK, Germany and the United States. The tests had been described in a series of “Red Books” issued by the British Fire Prevention Committee after 1903 in addition to those from the German Royal Technical Research Laboratory. The finalization of the ASTM standard was closely influenced by Professor I.H. เกจวัดแรงดันถังออกซิเจน , a Consulting Engineer of the USA National Board of Fire Underwriters and Chairman of the NFPA committee in Fire Resistive Construction who had carried out many tests at Columbia University and Underwriters Laboratories in Chicago. The small time temperature differences between the International ISO 834-1 test as we know it right now and the America ASTM E119 / NFPA 251 exams doubtless stemmed from this time.
Image courtesy of MICC Ltd.
The curve as we see it today (see graph above) has become the standard scale for measurement of fireplace take a look at severity and has proved relevant for many above floor cellulosic buildings. When elements, buildings, components or systems are examined, the furnace temperatures are managed to conform to the curve with a set allowable variance and consideration for preliminary ambient temperatures. The standards require elements to be tested in full scale and under situations of help and loading as outlined so as to symbolize as precisely as attainable its functions in service.
This Standard Time Temperature testing protocol (see graph right) is adopted by virtually all international locations around the world for fire testing and certification of virtually all building buildings, elements, systems and parts with the attention-grabbing exception of fire resistant cables (exception in USA, Canada, Australia, Germany, Belgium and New Zealand the place fire resistant cable systems are required to be examined and accredited to the Standard Time Temperature protocol, just like all other constructing constructions, components and components).
It is important to grasp that utility standards from BS, IEC, ASNZS, DIN, UL and so on. where fireplace resistive cables are specified for use, are only ‘minimum’ necessities. We know right now that fires are not all the same and analysis by Universities, Institutions and Authorities around the world have recognized that Underground and a few Industrial environments can exhibit very completely different hearth profiles to these in above floor cellulosic buildings. Specifically in confined underground public areas like Road and Rail Tunnels, Underground Shopping facilities, Car Parks fire temperatures can exhibit a very quick rise time and may reach temperatures properly above those in above ground buildings and in far much less time. In USA at present electrical wiring methods are required by NFPA 502 (Road Tunnels, Bridges and other Limited Access Highways) to face up to hearth temperatures up to 1,350 Degrees C for 60 minutes and UK British Standard BS8519:2010 clearly identifies underground public areas corresponding to automobile parks as “Areas of Special Risk” the place extra stringent check protocols for essential electric cable circuits could need to be thought of by designers.
Standard Time Temperature curves (Europe and America) plotted against widespread BS and IEC cable tests.
Of course all underground environments whether or not road, rail and pedestrian tunnels, or underground public environments like purchasing precincts, automotive parks and so forth. could exhibit totally different fire profiles to those in above ground buildings as a outcome of In these environments the heat generated by any hearth can’t escape as simply as it’d in above ground buildings thus relying extra on heat and smoke extraction gear.
For Metros Road and Rail Tunnels, Hospitals, Health care services, Underground public environments like purchasing precincts, Very High Rise, Theaters, Public Halls, Government buildings, Airports and so forth. this is particularly necessary. Evacuation of those public environments is usually sluggish even throughout emergencies, and it is our responsibility to ensure everyone appears to be given the perfect chance of secure egress throughout hearth emergencies.
It is also understood right now that copper Fire Resistant cables where put in in galvanized metal conduit can fail prematurely throughout fireplace emergency because of a response between the copper conductors and zinc galvanizing inside the steel conduit. In 2012 United Laboratories (UL®) in America removed all certification for Fire Resistive cables the place installed in galvanized steel conduit because of this:
UL® Quote: “A concern was delivered to our consideration related to the efficiency of these products in the presence of zinc. We validated this discovering. As a results of this, we modified our Guide Information to point that all conduit and conduit fittings that are obtainable in contact with fire resistive cables should have an interior coating free of zinc”.
Time temperature profile of tunnel fires utilizing automobiles, HGV trailers with totally different cargo and rail carriages. Graph extract: Haukur Ingason and Anders Lonnermark of the Swedish National Testing and Research Institute who presented the paper on the First International Symposium in Prague 2004: Safe and Reliable Tunnels.
It would seem that some Standards authorities around the world might need to evaluate the present test methodology at present adopted for hearth resistive cable testing and maybe align the efficiency of Life Safety and Fire Fighting wiring systems with that of all the opposite fire resistant constructions, parts and methods in order that Architects, constructing designers and engineers know that after they want a fireplace rating that the important wiring system might be equally rated.
For many energy, control, communication and data circuits there is one technology out there which can meet and surpass all current fire exams and applications. It is a solution which is incessantly used in demanding public buildings and has been employed reliably for over 80 years. MICC cable know-how can present a complete and full reply to all the problems associated with the hearth safety risks of contemporary flexible organic polymer cables.
The steel jacket, magnesium oxide insulation and conductors of MICC cables make positive the cable is successfully hearth proof. Bare MICC cables haven’t any organic content material so merely cannot propagate flame or generate any smoke. The zero fuel-load of those MICC cables ensures no heat is added to the fire and no oxygen is consumed. Being inorganic these MICC cables can not generate any halogen or poisonous gasses at all including Carbon Monoxide. MICC cable designs can meet the entire present and constructing hearth resistance efficiency standards in all nations and are seeing a significant improve in use globally.
Many engineers have previously thought of MICC cable expertise to be “old school’ however with the brand new analysis in fire efficiency MICC cable system are actually confirmed to have far superior fire performances than any of the newer extra fashionable flexible fire resistant cables.
For further info, go to www.temperature-house.com