How to prevent the ingress of moisture through the cable of submersible pressure transmitters and level probes?

If you want to measure the level of a liquid easily and reliably, most people will do this using hydrostatic pressure measurement, e.g. with a submersible pressure transmitter or a so called level probe. The characteristic submersed application implicates a maximum exposure to the encompassing, mainly water-based medium, respectively to ?moisture?.
Exposure isn’t only limited by the wetted elements of the pressure sensor housing, but additionally to the complete immersed amount of the cable. Furthermore, beyond your directly immersed level probe parts, the cable, and in particular the cable end, are often exposed to moisture due to splash water, rain and condensation. That is true not merely during operation, but even more during installation and commissioning, or when maintenance or retrofitting is necessary. Irrespective of the target application, whether in water and wastewater treatment or in tank monitoring, moisture ingress in to the cable ends of the submersible pressure transmitter can occur early and irreversibly with insufficient protection measures, and, in almost all cases, result in premature failure of the instrument.
The ingress of moisture into the cable outlet and from there on downwards in to the electronics of the level probe must be actively eliminated by preventive actions by an individual. To gauge the level with highest accuracy, the varying ambient pressure above the liquid media, which is also ?resting? on the liquid, should be compensated contrary to the hydrostatic pressure functioning on the pressure sensor (see article: hydrostatic level measurement).
Ventilation tube
Thus, it is logical that there is a constant threat of a moisture-related failure because of moisture ingress (both via the ventilation tube and through the actual cable itself) if there are no adequate protective measures. To compensate the ambient pressure ?resting? on the media, a ventilation tube runs from the sensor element within the particular level probe, through the cable and from the level probe by the end of the cable. Due to capillary action within the ventialation tube used for ambient pressure compensation, moisture can also be transported from the encompassing ambience right down to the sensor.
Thus not merely air, but also moisture penetrates into the tube, hence the sensor in the probe and the electronics around it is usually irreparably damaged. This can lead to measurement errors and, in the worst case, even to failure of the level probe. To prevent any premature failure, the ingress of moisture in to the ventilation tube must be completely prevented. Additional protection against moisture penetration through the ventilation tube is provided by fitting an air-permeable, but water-impermeable filter element by the end of the vent tube.
bare wires
Not to be ignored can be the transport of the liquid through high-humidity loads across the only limitedly protected internals of the cable, e.g. across the wires, completely down to the submersible pressure transmitter. As a respected manufacturer, WIKA uses appropriate structural design to prevent fluid transport, so far as possible, in to the electronics of the submersible pressure transmitter. Because of molecular diffusion and capillary effects, a guaranteed one-hundred percent protection over the full duration of the submersible pressure transmitter, however, is never achievable.
It is therefore recommended that the cable is definitely terminated in a waterproof junction box with the correct IP protection (e.g. IP65) which is matched to the installation location. If this cable junction box is exposed to weather and varying temperature conditions, additionally it is recommended to pay focus on a controlled pressure equalisation so as to avoid the formation of condensation or perspiration water and pumping effects. To address this technical requirement, as an accessory to a submersible pressure transmitter, it is possible to order a link box having an integrated air-permeable, water-impermeable membrane.
Ultimately, moisture ingress can occur not only through the exposed end of the cable, but also through mechanical harm to the cable sheath or because of liquid diffusion because of improper chemical resistance of the cable material. In the article ? Malicious for the prevention of moisture-related failures of submersible pressure transmitters or level probes? this failure mode is described in detail.
WIKA offers comprehensive solutions for the hydrostatic-pressure level measurement. For further assistance in selecting the submersible pressure transmitter most suitable for the application, please use our contact form.
Please find further information on this topic on our information platform ?Hydrostatic level measurement?